Voltage Drop Calculator

Calculate voltage drop in an AC or DC circuit given wire gauge, voltage, current, and length. You can also determine the correct conductor size and length for a circuit given an allowable voltage drop.

%
%

Voltage Drop:

In Volts:
0 volts
As a Percentage:
0%
End of Circuit Voltage:
0 volts

Conductor Diameter

inches:
0 in
millimeters:
0 mm

Conductor Cross-sectional Area

kcmil:
0 kcmil
square inches:
0 in2
square millimeters:
0 mm2
Learn how we calculated this below

scroll down


On this page:


How to Calculate Voltage Drop

Voltage drop is the amount of voltage lost in a circuit due to resistance of the conductor. Voltage drop is an important consideration when planning a circuit to allow equipment using the circuit to run as designed.

Voltage drop in a circuit means less voltage is delivered to connected devices. Electrical devices consume power, and when they get reduced voltages, the current flow increases to meet their power needs. This current increase can overheat the circuit, causing damage to the equipment and devices.

Using Ohm’s Law, the voltage can be calculated by multiplying the current by the resistance.

V(V) = I(A) × R(Ω)

Ohm’s Law states that the voltage is equal to the current times the resistance. You can find the resistance for various conductor sizes in the chart below, or use one of the following voltage drop formulas.

Voltage Drop Formula

Thus, you can calculate voltage drop for single-phase AC and DC circuits using the following formula derived from Ohm’s Law:[1]

Vdrop (V) = I(A) × 2 × ρ(Ω·m) × L(m) / A

Where:
V = allowable voltage drop in volts
I = current in amps
ρ = conductor resistivity in ohm-meters (Ω·m)
L = conductor length in meters
A = conductor cross-sectional area in square meters

So, the voltage dropped V in volts is equal to the current I in amps times 2 times the conductor resistivity ρ times the conductor length L in meters, divided by the cross-sectional area of the conductor A in square meters.

The resistivity of copper conductors is 1.7241 × 10-8 Ω·m and the resistivity of aluminum conductors is 2.6548 × 10-8 Ω·m.

Alternate Voltage Drop Formula

You may also see voltage drop calculated using an alternate formula, which calculates the conductor resistance in a slightly different way:[2]

Vdrop (V) = I(A) × 2 × K × L(m) / Amm²

Where:
V = allowable voltage drop in volts
K = direct current constant – use 12.9 for copper conductors and 21.2 for aluminum conductors. This is equal to the resistance of a conductor that is one thousand circular mils and one thousand feet in length.
I = current in amps
L = conductor length in meters
A = conductor cross-sectional area in square millimeters

voltage drop formula stating that voltage drop in volts is equal to the current in amps times the resistance in ohms

For example: Calculate the voltage drop of a 120V circuit drawing 15A using a 25′ long 14AWG copper conductor.


A 14 AWG wire has a cross-sectional area 2.081 mm² per the table below, and you can convert this to square meters by multiplying by 1,000,000. Recall that the resistivity of a copper conductor is 1.7241×10-8 Ω·m. You can convert the length in feet to meters by multiplying by 0.3048.

Vdrop (V) = 15A × 2 × 1.7241×10-8 × (25 ft × 0.3048 m⁄ft) / 2.081 m² × 1,000,000
Vdrop (V) = 15A × 0.1263Ω
Vdrop (V) = 1.894 V

So, we can expect a voltage drop of 1.894 volts in this circuit.

Voltage Drop Formula for Three-Phase Systems

The formula to calculate voltage drop in three-phase systems is

Vdrop (V) = I(A) × √3 × ρ(Ω·m) × L(m) / A

In a three-phase system, the voltage dropped V in volts is equal to the current I in amps times the square root of 3 times the conductor resistivity ρ times the conductor length L in meters, divided by the cross-sectional area of the conductor A in square meters.

How to Calculate the Minimum Conductor Size

Depending on the application, it is important to use conductors of the proper cross-sectional area for economical and reliable power delivery. A large conductor would be a waste of money, and an undersized conductor might not be able to handle the required current flows.

Using the equation for voltage drop and rearranging the variables, the minimum conductor size in square meters for a circuit can be found using the following:

A(m²) = 2 × ρ(Ω·m) × L(m) × I(A) / Vdrop (V)

Where:
A = cross-sectional area in square meters
ρ = conductor resistivity in ohm-meters (Ω·m)
L = length in meters
I = current in amps
V = allowable voltage drop in volts

The minimum cross-sectional area A for a conductor in square meters is equal to the product of two, the conductor resistivity ρ in Ω·m, its length L in meters, and the current I in amps, divided by the maximum allowable voltage drop V in volts.

You can multiply the resulting cross-sectional area by 1,000,000 to calculate the area in square millimeters. Then, use our wire size calculator to find the wire gauge with the correct cross-sectional area.

For example: Find the minimum wire gauge needed for a 120V circuit drawing 20A using a 40′ long copper conductor with a max voltage drop of 3%.


A 3% voltage drop would be 3.6 volts. Recall that the resistivity of a copper conductor is 1.7241×10-8 Ω·m. You can convert the length in feet to meters by multiplying by 0.3048.

A(m²) = 2 × 1.7241×10-8 × (40 ft × 0.3048 ft⁄m) × 20A / 3.6V
A(m²) = 2 × 1.7241×10-8 × 12.192 m × 20A / 3.6V
A(m²) = 8.408×10-6 / 3.6V
A(m²) = 2.3356×10-6

Then, multiply by 1,000,000 to convert the cross-sectional area in square meters to square millimeters.

A(mm²) = 2.3356×10-6 m² × 1,000,000
A(mm²) = 2.3356 mm²

Then, refer to the table below to find the minimum wire gauge for this cross-sectional area.

13 AWG

How to Calculate the Maximum Conductor Length

It is essential to use conductors of proper lengths to ensure minimal voltage drop in the conductive element. A longer conductor means the current must travel a longer distance through the conductive material and against more resistance.

This increase in resistance produces more voltage drops across the length of the circuit and causes it to overheat.

The maximum length of a conductor in a circuit can be determined by re-writing the formula for voltage drop like this:

L(m) = Vdrop (V) × A / 2 × ρ(Ω·m) × I(A)

Where:
V = allowable voltage drop in volts
I = current in amps
ρ = conductor resistivity in ohm-meters (Ω·m)
L = conductor length in meters
A = conductor cross-sectional area in square meters

The maximum conductor length is equal to the maximum allowable voltage drop V in volts times the cross-sectional area of the conductor in square meters, divided by 2 times the conductor resistivity ρ in Ω·m times the current I in amps.

Conductor Size and Resistance Table

Chart showing the cross-sectional area and resistance for various copper conductor sizes.
AWG Cross-Sectional Area Resistance
(kcmil) (mm²) Ohms per 1000ft Ohms per 1000m
0000 (4/0) 211.6 107.22 0.049 0.1608
000 (3/0) 167.81 85.029 0.0618 0.2028
00 (2/0) 133.08 67.431 0.0779 0.2557
0 (1/0) 105.53 53.475 0.0983 0.3224
1 83.693 42.408 0.1239 0.4066
2 66.371 33.631 0.1563 0.5127
3 52.635 26.67 0.197 0.6464
4 41.741 21.151 0.2485 0.8152
5 33.102 16.773 0.3133 1.028
6 26.251 13.302 0.3951 1.296
7 20.818 10.549 0.4982 1.634
8 16.51 8.366 0.6282 2.061
9 13.093 6.634 0.7921 2.599
10 10.383 5.261 0.9988 3.277
11 8.234 4.172 1.26 4.132
12 6.53 3.309 1.588 5.211
13 5.178 2.624 2.003 6.571
14 4.107 2.081 2.525 8.285
15 3.257 1.65 3.184 10.448
16 2.583 1.309 4.015 13.174
17 2.048 1.038 5.063 16.612
18 1.624 0.823 6.385 20.948
19 1.288 0.6527 8.051 26.415
20 1.022 0.5176 10.152 33.308
21 0.8101 0.4105 12.802 42.001
22 0.6424 0.3255 16.143 52.962
23 0.5095 0.2582 20.356 66.784
24 0.404 0.2047 25.668 84.213
25 0.3204 0.1624 32.367 106.19
26 0.2541 0.1288 40.814 133.9
27 0.2015 0.1021 51.466 168.85
28 0.1598 0.081 64.897 212.92
29 0.1267 0.0642 81.833 268.48
30 0.1005 0.0509 103.19 338.55
31 0.0797 0.0404 130.12 426.9
32 0.0632 0.032 164.08 538.32
33 0.0501 0.0254 206.9 678.8
34 0.0398 0.0201 260.9 855.96
35 0.0315 0.016 328.98 1,079.3
36 0.025 0.0127 414.84 1,361
37 0.0198 0.01 523.1 1,716.2
38 0.0157 0.007967 659.62 2,164.1
39 0.0125 0.006318 831.77 2,728.9
40 0.009888 0.00501 1,048.8 3,441.1

Also check out our electricity cost calculator to see how much it will cost to power a device.

References

  1. LibreTexts - Physics, University Physics II - Thermodynamics, Electricity, and Magnetism - 9.4: Resistivity and Resistance, https://phys.libretexts.org/Bookshelves/University_Physics/Book%3A_University_Physics_(OpenStax)/Book%3A_University_Physics_II_-_Thermodynamics_Electricity_and_Magnetism_(OpenStax)/09%3A_Current_and_Resistance/9.04%3A_Resistivity_and_Resistance
  2. IAEI Magazine, Voltage Drop Formulas, https://iaeimagazine.org/electrical-fundamentals/voltage-drop-formulas/